The 230V AC Proximity Sensor (AC Switch) you described is a two-wire AC-powered inductive or capacitive proximity sensor designed to function like a mechanical limit switch but without physical contact. Here’s a breakdown of its key features and applications:
230V AC Sensor
Typical Applications:
-
Replacement for mechanical limit switches in industrial automation.
-
Detection of metallic/non-metallic objects (depending on sensor type).
-
Control of relays, contactors, or PLC inputs in AC circuits.
-
Harsh environments (IP68 rating makes it suitable for wet/dusty conditions).
Important Considerations:
-
Load Compatibility: Ensure the connected load (PLC/relay) operates within the 200 mA limit.
-
Leakage Current (<2 mA): Some sensitive PLC inputs may still detect this as a “false ON”; a bypass resistor may be needed.
-
No Short-Circuit Protection: Use an external fuse if required.
Key Specifications:
-
Operating Principle:
-
Works like a two-wire AC switch (similar to a mechanical limit switch).
-
The load (PLC, relay, contactor, etc.) is connected in series with the sensor.
-
When the sensor detects a target, it allows current to flow (ON state); otherwise, it blocks current (OFF state, leakage <2mA).
-
-
Electrical Ratings:
-
Voltage Range: 50–250V AC
-
Switching Current: 200 mA (max)
-
Max Load Current: <400 mA
-
Voltage Drop: <6V at 200 mA
-
Leakage Current (OFF state): <2 mA
-
-
Sensing Performance:
-
Sensing Distance: 1mm–50mm (adjustable based on model)
-
Hysteresis: 5–10% of sensing distance
-
Repeatability: 5–10% of sensing distance
-
Switching Frequency: 50 Hz (suitable for standard AC applications)
-
-
Construction & Protection:
-
Housing Material: Chrome-plated brass (durable & corrosion-resistant)
-
Protection Class: IP68 (dustproof & waterproof)
-
Short Circuit Protection: No (external fuse recommended)
-
Polarity Protection: Yes (since it’s AC, polarity doesn’t matter)
-
-
Mounting & Wiring:
-
Mounting Options: Flush or non-flush (depending on application)
-
Cable: 2-core, 2 meters standard (custom lengths available)
-
Status Indicator: LED (for visual confirmation)
-